Browse papers
A

Section A: Long Answer Questions

Attempt all questions.

5 questions
1long10 marks

The recorded population of a hill town from the decennial census is given below.

Year (AD)19811991200120112021
Population24,00030,00038,00048,00062,000

(a) Estimate the population of the town for the design year 2041 using the arithmetic increase method and the geometric increase method. (6 marks)

(b) If the per-capita water demand is taken as 135 litres per capita per day (lpcd) and the peak factor for the maximum daily demand is 1.8, compute the maximum daily demand (in m³/day and in litres per second) for the design year 2041 using the geometric-method population. (4 marks)

(a) Population projection to 2041

The last census is 2021, so the design year 2041 is 2 decades ahead (n=2n = 2).

Decadal increases:

DecadeIncrease
1981→199130,000 − 24,000 = 6,000
1991→200138,000 − 30,000 = 8,000
2001→201148,000 − 38,000 = 10,000
2011→202162,000 − 48,000 = 14,000

Arithmetic increase method

Average decadal increase:

xˉ=6,000+8,000+10,000+14,0004=38,0004=9,500\bar{x} = \frac{6{,}000 + 8{,}000 + 10{,}000 + 14{,}000}{4} = \frac{38{,}000}{4} = 9{,}500 P2041=P2021+nxˉ=62,000+2(9,500)=62,000+19,000=81,000P_{2041} = P_{2021} + n\,\bar{x} = 62{,}000 + 2(9{,}500) = 62{,}000 + 19{,}000 = \mathbf{81{,}000}

Geometric increase method

Decadal growth rates:

DecadeRate
1981→19916,000/24,000 = 0.2500
1991→20018,000/30,000 = 0.2667
2001→201110,000/38,000 = 0.2632
2011→202114,000/48,000 = 0.2917

Geometric mean of growth ratios (1+r)(1+r):

1+r=(1.2500)(1.2667)(1.2632)(1.2917)41+r = \sqrt[4]{(1.2500)(1.2667)(1.2632)(1.2917)}

Product =1.2500×1.2667=1.58338= 1.2500 \times 1.2667 = 1.58338;   1.58338×1.2632=2.00014\;1.58338 \times 1.2632 = 2.00014;   2.00014×1.2917=2.58358\;2.00014 \times 1.2917 = 2.58358.

1+r=(2.58358)1/4=1.2680    r=0.2680 (26.80% per decade)1+r = (2.58358)^{1/4} = 1.2680 \;\Rightarrow\; r = 0.2680\ (26.80\%\ \text{per decade}) P2041=P2021(1+r)n=62,000(1.2680)2=62,000×1.60782=99,68599,700P_{2041} = P_{2021}(1+r)^n = 62{,}000\,(1.2680)^2 = 62{,}000 \times 1.60782 = \mathbf{99{,}685 \approx 99{,}700}

(b) Maximum daily demand for 2041 (geometric population)

Use P2041=99,685P_{2041} = 99{,}685, demand =135= 135 lpcd, peak factor =1.8= 1.8.

Average daily demand:

Qavg=99,685×1351000=13,457.5 m3/dayQ_{avg} = \frac{99{,}685 \times 135}{1000} = 13{,}457.5\ \text{m}^3/\text{day}

Maximum daily demand:

Qmax=1.8×13,457.5=24,223.5 m3/dayQ_{max} = 1.8 \times 13{,}457.5 = 24{,}223.5\ \text{m}^3/\text{day}

Convert to litres per second:

Qmax=24,223.5×100086,400=280.4 L/sQ_{max} = \frac{24{,}223.5 \times 1000}{86{,}400} = 280.4\ \text{L/s}

Maximum daily demand ≈ 24,224 m³/day ≈ 280.4 L/s.

population-forecastingwater-demand
2long10 marks

A rectangular continuous-flow sedimentation tank is to be designed to treat 18 MLD (million litres per day) of water. Adopt a surface overflow rate (overflow velocity) of 30 m³/m²/day and a detention time of 3 hours.

(a) Determine the required surface area and plan dimensions, taking a length-to-width ratio of 4:1. (4 marks)

(b) Determine the required depth and the tank volume; verify the detention time. (3 marks)

(c) A discrete particle of diameter 0.02 mm and specific gravity 2.65 settles in water at 20 °C (μ=1.005×103 N\cdotps/m2\mu = 1.005 \times 10^{-3}\ \text{N·s/m}^2). Using Stokes' law, find the settling velocity and state whether the particle will be removed in this tank. (3 marks)

Given

Q=18 MLD=18,000 m3/dayQ = 18\ \text{MLD} = 18{,}000\ \text{m}^3/\text{day}; overflow rate v0=30 m3/m2/dayv_0 = 30\ \text{m}^3/\text{m}^2/\text{day}; detention t=3 ht = 3\ \text{h}.

(a) Surface area and plan dimensions

A=Qv0=18,00030=600 m2A = \frac{Q}{v_0} = \frac{18{,}000}{30} = 600\ \text{m}^2

With L=4BL = 4B:   A=L×B=4B2=600B2=150B=12.25 m\;A = L\times B = 4B^2 = 600 \Rightarrow B^2 = 150 \Rightarrow B = 12.25\ \text{m}.

L=4×12.25=49.0 mL = 4 \times 12.25 = 49.0\ \text{m}

Adopt L = 49.0 m, B = 12.25 m (area = 600.25 m² ≈ 600 m²).

(b) Depth, volume and detention check

Volume required for 3 h detention:

V=Q×t=18,000 m3/day×324 day=2,250 m3V = Q \times t = 18{,}000\ \text{m}^3/\text{day} \times \frac{3}{24}\ \text{day} = 2{,}250\ \text{m}^3

Depth:

H=VA=2,250600=3.75 mH = \frac{V}{A} = \frac{2{,}250}{600} = 3.75\ \text{m}

Check detention time: t=V/Q=2,250/18,000=0.125 day=3.0 ht = V/Q = 2{,}250 / 18{,}000 = 0.125\ \text{day} = 3.0\ \text{h}

Adopt depth = 3.75 m (plus free board ≈ 0.5 m).

(c) Stokes' law settling velocity

d=0.02 mm=2×105 md = 0.02\ \text{mm} = 2 \times 10^{-5}\ \text{m}, Gs=2.65G_s = 2.65, μ=1.005×103 N\cdotps/m2\mu = 1.005\times 10^{-3}\ \text{N·s/m}^2.

vs=g(Gs1)d218ν(using kinematic form)=g(ρsρw)d218μv_s = \frac{g\,(G_s - 1)\,d^2}{18\,\nu}\quad\text{(using kinematic form)} = \frac{g\,(\rho_s-\rho_w)\,d^2}{18\,\mu} vs=9.81×(26501000)×(2×105)218×1.005×103v_s = \frac{9.81 \times (2650-1000) \times (2\times10^{-5})^2}{18 \times 1.005\times10^{-3}}

Numerator =9.81×1650×4×1010=6.4746×106= 9.81 \times 1650 \times 4\times10^{-10} = 6.4746\times10^{-6}. Denominator =0.01809= 0.01809.

vs=6.4746×1060.01809=3.578×104 m/sv_s = \frac{6.4746\times10^{-6}}{0.01809} = 3.578\times10^{-4}\ \text{m/s}

Convert overflow rate to m/s: v0=30 m/day=30/86400=3.472×104 m/sv_0 = 30\ \text{m/day} = 30/86400 = 3.472\times10^{-4}\ \text{m/s}.

Since vs=3.58×104 m/s>v0=3.47×104 m/sv_s = 3.58\times10^{-4}\ \text{m/s} > v_0 = 3.47\times10^{-4}\ \text{m/s}, the particle settling velocity exceeds the overflow rate, so the particle WILL be fully removed in the tank.

(Check Reynolds number: Re=vsd/ν=3.578×104×2×105/(1.005×106)=0.0071<1Re = v_s d/\nu = 3.578\times10^{-4}\times2\times10^{-5}/(1.005\times10^{-6}) = 0.0071 < 1, so Stokes' law is valid.)

sedimentationtreatment-design
3long10 marks

A water treatment plant treats 24 MLD. It is to be filtered through rapid gravity sand filters designed at a filtration rate of 5000 litres/m²/hour.

(a) Determine the total filter area required and the number of filter units if each unit is limited to a plan area of about 40 m². Provide one extra unit as a stand-by. (4 marks)

(b) For backwashing, a wash-water rate of 0.5 m³/m²/min is applied for 8 minutes per unit. Each unit is washed once per day. Express the daily wash-water volume as a percentage of the daily filtered output. (3 marks)

(c) State two functions of the gravel support layer and two functions of the under-drainage system, and briefly explain negative head in a rapid sand filter. (3 marks)

Given

Q=24 MLD=24,000,000 L/dayQ = 24\ \text{MLD} = 24{,}000{,}000\ \text{L/day}; filtration rate =5000 L/m2/h= 5000\ \text{L/m}^2/\text{h}.

(a) Filter area and number of units

Daily filtration capacity per m²: 5000 L/m2/h×24 h=120,000 L/m2/day=120 m3/m2/day5000\ \text{L/m}^2/\text{h} \times 24\ \text{h} = 120{,}000\ \text{L/m}^2/\text{day} = 120\ \text{m}^3/\text{m}^2/\text{day}.

Total area:

A=24,000120=200 m2A = \frac{24{,}000}{120} = 200\ \text{m}^2

Number of working units at 40 m² each: 200/40=5200/40 = 5 units.

Provide 1 stand-bytotal 6 units. (When one unit is washed/down, the remaining 5 still deliver design flow.)

Actual area per working unit when all 6 are in service can be checked, but design adopts 6 units of 40 m² each (5 working + 1 stand-by).

(b) Wash-water as percentage of output

Area of one unit =40 m2= 40\ \text{m}^2. Wash rate =0.5 m3/m2/min= 0.5\ \text{m}^3/\text{m}^2/\text{min} for 8 min8\ \text{min}.

Wash water per unit per wash:

=0.5×40×8=160 m3= 0.5 \times 40 \times 8 = 160\ \text{m}^3

There are 5 working units (each washed once/day); total daily wash water:

=160×5=800 m3/day= 160 \times 5 = 800\ \text{m}^3/\text{day}

Daily filtered output =24,000 m3/day= 24{,}000\ \text{m}^3/\text{day}.

% wash water=80024,000×100=3.33%\%\text{ wash water} = \frac{800}{24{,}000}\times100 = 3.33\%

Wash water ≈ 3.33% of filtered output (within the acceptable 2–6% range).

(c) Functions

Gravel support layer:

  1. Supports the fine sand bed and prevents fine media from passing into the under-drains.
  2. Distributes the rising backwash water uniformly across the filter bottom.

Under-drainage system:

  1. Collects the filtered water and conveys it to the clear-water well.
  2. Distributes backwash water (and air, if used) evenly during cleaning of the bed.

Negative head: As the filter run progresses the sand bed clogs and head loss through the upper layers increases. If the head loss exceeds the depth of water standing above a given level in the bed, the pressure there falls below atmospheric (a partial vacuum), called negative head. It causes release of dissolved gases (air binding) which further blocks the pores and reduces the filtration rate; backwashing is then required.

rapid-sand-filterfiltration
4long10 marks

A single closed loop ABCD of a water distribution network carries the inflows and outflows shown. Inflow of 120 L/s enters at A; demands are withdrawn at B (40 L/s), C (30 L/s) and D (50 L/s). Pipe head-loss is expressed as hf=KQ2h_f = K Q^2 with the following KK values (consistent units, QQ in L/s):

PipeABBCCDDA
K0.00200.00500.00300.0010

Assume an initial clockwise (A→B→C→D→A) flow distribution: QAB=+70Q_{AB}=+70, QBC=+30Q_{BC}=+30, QCD=0Q_{CD}=0, QDA=50Q_{DA}=-50 (L/s).

(a) Perform one iteration of the Hardy-Cross method to compute the corrected flow in each pipe. (8 marks)

(b) Using the corrected flow, compute the head loss in pipe AB after the first iteration. (2 marks)

Hardy-Cross correction formula

For a loop with hf=KQ2h_f = KQ^2:

Δ=KQQ2KQ\Delta = -\frac{\sum K Q |Q|}{\sum 2K|Q|}

Taking clockwise as positive. Initial assumed flows satisfy continuity:

  • Node A: in 120, out to AB (70) and from DA. Check node B: in 70, out 40, to BC 30 ✓. Node C: in 30, out 30, CD 0 ✓. Node D: CD in 0, DA out 50, demand 50 ✓.

Iteration 1 – build the table

| Pipe | K | Q (L/s) | KQQKQ|Q| | 2KQ2K|Q| | |------|------|---------|---------|---------| | AB | 0.0020 | +70 | 0.0020·70·70 = +9.800 | 2·0.0020·70 = 0.280 | | BC | 0.0050 | +30 | 0.0050·30·30 = +4.500 | 2·0.0050·30 = 0.300 | | CD | 0.0030 | 0 | 0.000 | 0.000 | | DA | 0.0010 | −50 | 0.0010·(−50)·50 = −2.500 | 2·0.0010·50 = 0.100 |

KQQ=9.800+4.500+0.0002.500=+11.800\sum KQ|Q| = 9.800 + 4.500 + 0.000 - 2.500 = +11.800 2KQ=0.280+0.300+0.000+0.100=0.680\sum 2K|Q| = 0.280 + 0.300 + 0.000 + 0.100 = 0.680

Correction

Δ=11.8000.680=17.35 L/s\Delta = -\frac{11.800}{0.680} = -17.35\ \text{L/s}

Apply Δ\Delta to every pipe of the loop (add algebraically, keeping sign convention):

PipeQoldQ_{old}Qnew=Qold+ΔQ_{new} = Q_{old}+\Delta
AB+7070 − 17.35 = +52.65
BC+3030 − 17.35 = +12.65
CD00 − 17.35 = −17.35
DA−50−50 − 17.35 = −67.35

Corrected flows after one iteration

  • QAB=52.65 L/sQ_{AB} = 52.65\ \text{L/s} (A→B)
  • QBC=12.65 L/sQ_{BC} = 12.65\ \text{L/s} (B→C)
  • QCD=17.35 L/sQ_{CD} = 17.35\ \text{L/s} (C→D direction reversed to D→C, i.e. flow actually D→C)
  • QDA=67.35 L/sQ_{DA} = 67.35\ \text{L/s} (flow A→D since sign negative w.r.t. clockwise)

Continuity re-check at B: in 52.65, out demand 40 + BC 12.65 = 52.65 ✓.

A further iteration would be performed until Δ|\Delta| \le allowable (≈ 0.1–1 L/s); after one iteration Δ=17.35\Delta = -17.35 L/s is still large, so iteration continues in practice.

(b) Head loss in pipe AB after first iteration

Using corrected QAB=52.65 L/sQ_{AB} = 52.65\ \text{L/s} and KAB=0.0020K_{AB} = 0.0020:

hf,AB=KQ2=0.0020×(52.65)2=0.0020×2772.0=5.544 (head-loss units)h_{f,AB} = K Q^2 = 0.0020 \times (52.65)^2 = 0.0020 \times 2772.0 = 5.544\ \text{(head-loss units)}

Head loss in AB ≈ 5.54 m (in the consistent units of KK).

distribution-systemhardy-cross
5long10 marks

A centrifugal pump lifts 40 L/s of water from a sump to an overhead reservoir. The static lift is 35 m. The total length of the rising main (cast-iron, diameter 250 mm) is 480 m with a Darcy friction factor f=0.024f = 0.024. Minor losses may be taken as 15% of the friction loss.

(a) Compute the total dynamic head (manometric head) on the pump. (5 marks)

(b) If the combined efficiency of pump and motor is 72%, compute the power input required (kW) and the energy consumed per day if the pump runs 16 hours/day. (3 marks)

(c) Define water hammer and state two devices used to control it in a pumping main. (2 marks)

Given

Q=40 L/s=0.040 m3/sQ = 40\ \text{L/s} = 0.040\ \text{m}^3/\text{s}; static lift Hs=35 mH_s = 35\ \text{m}; D=0.250 mD = 0.250\ \text{m}; L=480 mL = 480\ \text{m}; f=0.024f = 0.024.

(a) Total dynamic head

Velocity in rising main:

A=π4D2=π4(0.250)2=0.04909 m2A = \frac{\pi}{4}D^2 = \frac{\pi}{4}(0.250)^2 = 0.04909\ \text{m}^2 V=QA=0.0400.04909=0.8149 m/sV = \frac{Q}{A} = \frac{0.040}{0.04909} = 0.8149\ \text{m/s}

Friction loss (Darcy–Weisbach):

hf=fLV22gD=0.024×480×(0.8149)22×9.81×0.250h_f = \frac{f L V^2}{2 g D} = \frac{0.024 \times 480 \times (0.8149)^2}{2 \times 9.81 \times 0.250}

Numerator =0.024×480×0.66406=7.6516= 0.024 \times 480 \times 0.66406 = 7.6516. Denominator =4.905= 4.905.

hf=7.65164.905=1.560 mh_f = \frac{7.6516}{4.905} = 1.560\ \text{m}

Minor losses =0.15×hf=0.15×1.560=0.234 m= 0.15 \times h_f = 0.15 \times 1.560 = 0.234\ \text{m}.

Velocity head (delivered) =V2/2g=0.66406/19.62=0.034 m= V^2/2g = 0.66406/19.62 = 0.034\ \text{m} (small, may be included).

Total dynamic head:

H=Hs+hf+hminor+V22g=35+1.560+0.234+0.034=36.83 mH = H_s + h_f + h_{minor} + \frac{V^2}{2g} = 35 + 1.560 + 0.234 + 0.034 = 36.83\ \text{m}

Total dynamic (manometric) head H ≈ 36.83 m (≈ 36.8 m if velocity head neglected: 36.79 m).

(b) Power input and daily energy

Water (output) power:

Pwater=ρgQH=1000×9.81×0.040×36.83=14,452 W=14.45 kWP_{water} = \rho g Q H = 1000 \times 9.81 \times 0.040 \times 36.83 = 14{,}452\ \text{W} = 14.45\ \text{kW}

Input power at overall efficiency η=0.72\eta = 0.72:

Pinput=Pwaterη=14.450.72=20.07 kWP_{input} = \frac{P_{water}}{\eta} = \frac{14.45}{0.72} = 20.07\ \text{kW}

Daily energy (16 h/day):

E=20.07 kW×16 h=321.1 kWh/dayE = 20.07\ \text{kW} \times 16\ \text{h} = 321.1\ \text{kWh/day}

Power input ≈ 20.07 kW; daily energy ≈ 321 kWh/day.

(c) Water hammer

Water hammer is the sudden rise (and subsequent oscillation) of pressure in a pipeline caused by a rapid change in the velocity of flow — for example when a valve is closed quickly or a pump trips. The momentum of the moving water column is abruptly arrested, producing a pressure surge that can burst pipes or damage fittings.

Two control devices: (i) Air vessel / surge tank (absorbs and cushions the pressure surge); (ii) Slow-closing or automatic relief/non-return valves (limit the rate of velocity change and release excess pressure). Flywheels on pump motors are also used to slow the velocity change.

pumpingpump-power
B

Section B: Short Answer Questions

Attempt all questions.

6 questions
6short5 marks

(a) A water supply requires a chlorine dose of 2.5 mg/L to treat 6 MLD. The chlorine demand of the water is 1.8 mg/L. Compute the mass of chlorine required per day and the residual chlorine maintained. (3 marks)

(b) Define break-point chlorination and state why a free chlorine residual is desirable. (2 marks)

(a) Chlorine mass and residual

Q=6 MLD=6×106 L/day=6,000 m3/dayQ = 6\ \text{MLD} = 6 \times 10^{6}\ \text{L/day} = 6{,}000\ \text{m}^3/\text{day}; dose =2.5 mg/L= 2.5\ \text{mg/L}.

Mass of chlorine per day:

M=dose×Q=2.5 mgL×6×106 Lday=15×106 mg/dayM = \text{dose} \times Q = 2.5\ \frac{\text{mg}}{\text{L}} \times 6\times10^{6}\ \frac{\text{L}}{\text{day}} = 15 \times 10^{6}\ \text{mg/day} =15,000,000 mg/day=15 kg/day= 15{,}000{,}000\ \text{mg/day} = 15\ \text{kg/day}

Residual chlorine == dose - demand =2.51.8=0.7 mg/L= 2.5 - 1.8 = 0.7\ \text{mg/L}.

Chlorine required = 15 kg/day; residual maintained = 0.7 mg/L (within the recommended 0.2–0.5 mg/L free residual range at the consumer end after travel; at the plant 0.7 mg/L is acceptable).

(b) Break-point chlorination

Break-point chlorination is the application of chlorine in a dose large enough to satisfy the entire chlorine demand — oxidising organics, ammonia and reducing compounds and destroying chloramines — so that any chlorine added beyond the break point appears as free available chlorine residual.

A free chlorine residual is desirable because:

  • It provides a continued disinfecting (residual) capacity throughout the distribution system, guarding against re-contamination.
  • Free chlorine is a stronger and faster disinfectant than combined (chloramine) residual and serves as an indicator that disinfection is adequate.
disinfectionchlorination
7short5 marks

A treatment plant treating 10 MLD uses filter alum [Al2(SO4)314H2O][\text{Al}_2(\text{SO}_4)_3\cdot 14H_2O] at a dose of 30 mg/L.

(a) Compute the daily alum requirement (kg/day). (2 marks)

(b) Each mg/L of alum consumes alkalinity; the reaction consumes about 0.45 mg/L of alkalinity (as CaCO₃) per mg/L of alum. Determine whether natural alkalinity of 18 mg/L (as CaCO₃) is sufficient, and if not, the dose of quicklime (CaO) needed, given that 0.35 mg of CaO neutralises/supplies 1 mg of alkalinity as CaCO₃ deficit (i.e. CaO needed = 0.35 × alkalinity deficit). (3 marks)

(a) Daily alum requirement

Q=10 MLD=10×106 L/dayQ = 10\ \text{MLD} = 10 \times 10^{6}\ \text{L/day}; dose =30 mg/L= 30\ \text{mg/L}.

Malum=30 mgL×10×106 Lday=300×106 mg/day=300 kg/dayM_{alum} = 30\ \frac{\text{mg}}{\text{L}} \times 10\times10^{6}\ \frac{\text{L}}{\text{day}} = 300\times10^{6}\ \text{mg/day} = 300\ \text{kg/day}

Alum requirement = 300 kg/day.

(b) Alkalinity check and lime dose

Alkalinity required to react with alum:

=0.45×alum dose=0.45×30=13.5 mg/L (as CaCO3)= 0.45 \times \text{alum dose} = 0.45 \times 30 = 13.5\ \text{mg/L (as CaCO}_3)

Natural alkalinity available =18 mg/L= 18\ \text{mg/L}.

Since 18 mg/L>13.5 mg/L18\ \text{mg/L} > 13.5\ \text{mg/L}, the natural alkalinity IS sufficient; there is a surplus of 1813.5=4.5 mg/L18 - 13.5 = 4.5\ \text{mg/L} as CaCO₃.

No quicklime addition is required for coagulation.

(If alkalinity had been deficient, the lime dose would be CaO =0.35×= 0.35 \times deficit. Here deficit =0= 0, so CaO =0= 0 mg/L.)

coagulationalum-dose
8short5 marks

(a) Differentiate between surface sources and groundwater sources of water supply, giving two points each on quality and reliability. (3 marks)

(b) List four important physical, chemical or bacteriological parameters tested for drinking water and state the maximum permissible value of any TWO of them as per the Nepal Drinking Water Quality Standards (NDWQS 2005/2062). (2 marks)

(a) Surface vs groundwater sources

AspectSurface sources (rivers, lakes, reservoirs)Groundwater (springs, wells, tube-wells)
Turbidity / physical qualityGenerally turbid, high suspended solids; needs full treatmentUsually clear, low turbidity; little/no filtration needed
Bacteriological qualityMore exposed to contamination/pathogensNaturally filtered, generally safer bacteriologically
Mineral/chemical contentLower dissolved minerals; softer waterHigher dissolved minerals (hardness, Fe, Mn, sometimes arsenic)
Reliability / quantityLarge quantity but flow varies seasonallyMore dependable in dry season but yield limited by aquifer

(Any two valid points on quality and on reliability earn full marks.)

(b) Drinking-water parameters and NDWQS limits

Four parameters: turbidity, pH, total hardness (as CaCO₃), and total/faecal coliform (bacteriological). Others: arsenic, iron, chloride, nitrate.

Maximum permissible values per NDWQS 2005 (examples):

  • Turbidity: 5 NTU (max permissible 10 NTU)
  • pH: 6.5 – 8.5
  • Total hardness (as CaCO₃): 500 mg/L
  • Arsenic: 0.05 mg/L
  • E. coli / total coliform: 0 per 100 mL (must be absent)

(Stating any two correctly is sufficient for the 2 marks.)

sourceswater-quality
9short5 marks

A gravity-fed rural water supply scheme serves a village with a design population of 600 persons at 45 lpcd. The reservoir (RVT) is sized to store 50% of the average daily demand.

(a) Compute the average daily demand (litres/day). (1.5 marks)

(b) Compute the required storage capacity of the reservoir (m³). (1.5 marks)

(c) If water is collected from the source over only 12 hours per day, compute the required source/supply flow rate in litres per minute. (1 mark)

(d) State one reason why distribution storage is provided in such schemes. (1 mark)

(a) Average daily demand

Q=600 persons×45 lpcd=27,000 L/dayQ = 600\ \text{persons} \times 45\ \text{lpcd} = 27{,}000\ \text{L/day}

Average daily demand = 27,000 L/day (= 27 m³/day).

(b) Reservoir storage capacity

Storage =50%= 50\% of average daily demand:

V=0.50×27,000=13,500 L=13.5 m3V = 0.50 \times 27{,}000 = 13{,}500\ \text{L} = 13.5\ \text{m}^3

Required storage capacity = 13.5 m³.

(c) Source flow if collected over 12 hours

q=27,000 L/day12 h×60 min/h=27,000720=37.5 L/minq = \frac{27{,}000\ \text{L/day}}{12\ \text{h} \times 60\ \text{min/h}} = \frac{27{,}000}{720} = 37.5\ \text{L/min}

Required source supply rate = 37.5 L/min (≈ 0.625 L/s).

(d) Reason for distribution (service) storage

It balances the variation between the steady source/supply inflow and the fluctuating hourly demand of the village — storing water during low-demand (night) hours and meeting peak (morning/evening) draw-off, while also providing a reserve during source interruption or maintenance.

rural-water-supplyservice-reservoir
10short5 marks

(a) With neat sketches (described), explain any TWO layouts of distribution systems (dead-end, grid-iron, ring/circular, radial) and state one advantage of each. (3 marks)

(b) Name three valves/appurtenances used in a distribution network and state the function of each. (2 marks)

(a) Distribution-system layouts

1. Dead-end (tree) system

        main
  o-----+-----+-----+-----o
        |     |     |
        +     +     +   (branch sub-mains, dead ends)

Water flows from one main to progressively smaller branches that terminate in dead ends. Advantage: Simple to design and lay; fewer pipes and valves, hence economical and easy to compute discharges.

2. Grid-iron (interconnected) system

  +----+----+----+
  |    |    |    |
  +----+----+----+
  |    |    |    |
  +----+----+----+

Mains and sub-mains are interconnected so water can reach any point by more than one path. Advantage: No dead ends — water remains fresh (less stagnation), and during a repair flow is maintained from alternate routes; better pressure distribution.

(Ring system: a closed loop main surrounding the area — advantage: any node fed from two directions. Radial system: water pumped outward from central reservoirs — advantage: high pressure and quick service.)

(b) Valves / appurtenances

  • Sluice (gate) valve: isolates a pipe section for repair by stopping flow.
  • Air-relief valve: releases accumulated air at summits to prevent air locks and pressure problems.
  • Scour (washout) valve: placed at low points to flush out accumulated silt/sediment from the mains; a check (reflux/non-return) valve prevents reverse flow on a pumping main.
distribution-layoutpipe-appurtenances
11short5 marks

A city has a design population of 150,000. The average domestic demand is 150 lpcd.

(a) Compute the average daily domestic demand (m³/day). (1.5 marks)

(b) Using the Kuichling/Freeman type empirical fire-demand formula Q=4637P(10.01P)Q = 4637\sqrt{P}\,(1 - 0.01\sqrt{P}) (Q in L/min, P in thousands), estimate the fire demand. (2.5 marks)

(c) State the coincident-draft principle for sizing the supply (which is added to which). (1 mark)

(a) Average daily domestic demand

Qdom=150,000×150 lpcd=22,500,000 L/day=22,500 m3/dayQ_{dom} = 150{,}000 \times 150\ \text{lpcd} = 22{,}500{,}000\ \text{L/day} = 22{,}500\ \text{m}^3/\text{day}

Average daily domestic demand = 22,500 m³/day.

(b) Fire demand (Freeman-type formula)

P=150P = 150 (population in thousands), P=150=12.247\sqrt{P} = \sqrt{150} = 12.247.

Q=4637P(10.01P)=4637×12.247×(10.01×12.247)Q = 4637\sqrt{P}\,(1 - 0.01\sqrt{P}) = 4637 \times 12.247 \times (1 - 0.01\times12.247)

=4637×12.247×(10.12247)= 4637 \times 12.247 \times (1 - 0.12247) =4637×12.247×0.87753= 4637 \times 12.247 \times 0.87753

4637×12.247=56,7894637 \times 12.247 = 56{,}789 (L/min, before factor). 56,789×0.87753=49,833 L/min56{,}789 \times 0.87753 = 49{,}833\ \text{L/min}.

Convert to daily volume: 49,833 L/min×1440 min/day=71.76×106 L/day71,760 m3/day49{,}833\ \text{L/min} \times 1440\ \text{min/day} = 71.76 \times 10^{6}\ \text{L/day} \approx 71{,}760\ \text{m}^3/\text{day} (if sustained 24 h; usually applied for a few hours).

Fire demand ≈ 49,833 L/min ≈ 830 L/s.

(c) Coincident-draft principle

Fire demand is not added to the average demand. It is provided in addition to the maximum daily demand, because a fire is assumed to occur at a time of high (maximum daily) consumption. Thus the design draft (for source/pump/main capacity) is taken as the greater of (maximum hourly demand) and (maximum daily demand + fire demand).

water-demandfire-demand

Frequently asked questions

Where can I find the BE Civil Engineering (IOE, TU) Water Supply Engineering (IOE, CE 651) question paper 2079?
The full BE Civil Engineering (IOE, TU) Water Supply Engineering (IOE, CE 651) 2079 (regular) question paper is available free on Kekkei. You can read every question online and attempt the paper under timed exam conditions.
Does the Water Supply Engineering (IOE, CE 651) 2079 paper come with solutions?
Yes. Every question on this Water Supply Engineering (IOE, CE 651) past paper includes a step-by-step solution, plus instant AI feedback when you attempt it on Kekkei.
How many marks is the BE Civil Engineering (IOE, TU) Water Supply Engineering (IOE, CE 651) 2079 paper?
The BE Civil Engineering (IOE, TU) Water Supply Engineering (IOE, CE 651) 2079 paper carries 80 full marks and is meant to be completed in 180 minutes, across 11 questions.
Is practising this Water Supply Engineering (IOE, CE 651) past paper free?
Yes — reading and attempting this Water Supply Engineering (IOE, CE 651) past paper on Kekkei is completely free.