Browse papers
A

Section A: Long Answer Questions

Attempt all / any as specified.

4 questions
1long12 marks

(a) State and explain Thevenin's theorem. Outline the step-by-step procedure for obtaining the Thevenin equivalent of a linear network containing both independent and dependent sources. [6]

(b) For the network shown below, a 24 V source is connected across terminals A-B through a 4 Ω resistor, with a 6 Ω resistor in series feeding node C, and a 12 Ω resistor from C to ground. Determine the Thevenin equivalent (V_Th and R_Th) seen by a load resistor R_L connected between node C and ground, and hence find the value of R_L for maximum power transfer and the corresponding maximum power delivered to it. [6]

(a) Thevenin's Theorem

Statement: Any linear, bilateral two-terminal network containing sources and resistances can be replaced, with respect to two terminals A-B, by a single voltage source VThV_{Th} in series with a single resistance RThR_{Th}, where VThV_{Th} is the open-circuit voltage across A-B and RThR_{Th} is the equivalent resistance seen from A-B with all independent sources deactivated.

Procedure (network with independent and dependent sources):

  1. Remove the load RLR_L from terminals A-B.
  2. Find the open-circuit voltage VTh=VOCV_{Th} = V_{OC} across A-B (mesh/nodal analysis).
  3. To find RThR_{Th}:
    • If only independent sources: deactivate them (replace voltage sources by short circuits, current sources by open circuits) and compute the resistance looking into A-B.
    • If dependent sources are present: deactivate only the independent sources, apply a test source VtV_t (or ItI_t) at A-B, and compute RTh=Vt/ItR_{Th} = V_t / I_t. Alternatively, RTh=VOC/ISCR_{Th} = V_{OC} / I_{SC}, where ISCI_{SC} is the short-circuit current.
  4. Draw the Thevenin equivalent: VThV_{Th} in series with RThR_{Th}, then reconnect RLR_L.

(b) Numerical

With the load removed at node C (open circuit), the 24 V source drives current through 4Ω+6Ω4\,\Omega + 6\,\Omega in series, then through the 12Ω12\,\Omega to ground.

Open-circuit voltage (voltage divider across the 12Ω12\,\Omega):

VTh=24×124+6+12=24×1222=13.09 VV_{Th} = 24 \times \frac{12}{4 + 6 + 12} = 24 \times \frac{12}{22} = 13.09\ \text{V}

Thevenin resistance (24 V source shorted): looking into C-ground, the 12Ω12\,\Omega is in parallel with (4+6)=10Ω(4+6)=10\,\Omega:

RTh=12×1012+10=12022=5.45 ΩR_{Th} = \frac{12 \times 10}{12 + 10} = \frac{120}{22} = 5.45\ \Omega

Maximum power transfer: RL=RTh=5.45 ΩR_L = R_{Th} = 5.45\ \Omega.

Pmax=VTh24RTh=(13.09)24×5.45=171.421.8=7.86 WP_{max} = \frac{V_{Th}^2}{4R_{Th}} = \frac{(13.09)^2}{4 \times 5.45} = \frac{171.4}{21.8} = 7.86\ \text{W}
dc-circuitsnetwork-theoremsthevenin
2long12 marks

(a) Derive the EMF equation of a single-phase transformer and define its transformation ratio. [5]

(b) A 25 kVA, 2200/220 V, 50 Hz single-phase transformer gave the following test results: Open-circuit test (LV side): 220 V, 1.5 A, 90 W; Short-circuit test (HV side): 75 V, 11.4 A, 280 W. Draw the approximate equivalent circuit referred to the HV side and determine the efficiency and percentage voltage regulation at full load, 0.8 power factor lagging. [7]

(a) EMF Equation of a Single-Phase Transformer

When a sinusoidal flux ϕ=ϕmsinωt\phi = \phi_m \sin\omega t links a winding of NN turns, the induced EMF is e=Ndϕ/dte = -N\,d\phi/dt. The flux rises from 0 to ϕm\phi_m in a quarter cycle (1/4f)(1/4f) seconds, so the average rate of change is ϕm1/4f=4fϕm\frac{\phi_m}{1/4f} = 4f\phi_m, giving average EMF per turn =4fϕm= 4f\phi_m.

For a sinusoid, RMS = form factor (1.11) × average:

E=1.11×4fϕmN=4.44fNϕmE = 1.11 \times 4f\phi_m N = 4.44\,f\,N\,\phi_m

Thus E1=4.44fN1ϕmE_1 = 4.44 f N_1 \phi_m and E2=4.44fN2ϕmE_2 = 4.44 f N_2 \phi_m.

Transformation ratio:

K=E2E1=N2N1=V2V1=I1I2K = \frac{E_2}{E_1} = \frac{N_2}{N_1} = \frac{V_2}{V_1} = \frac{I_1}{I_2}

(b) Numerical (referred to HV side)

Rated HV current I2=250002200=11.36 AI_2 = \dfrac{25000}{2200} = 11.36\ \text{A}.

From SC test (HV side): Vsc=75V_{sc}=75\,V, Isc=11.4I_{sc}=11.4\,A, Wsc=280W_{sc}=280\,W

Zeq=7511.4=6.58 Ω,Req=28011.42=2.15 Ω,Xeq=6.5822.152=6.22 ΩZ_{eq} = \frac{75}{11.4} = 6.58\ \Omega,\quad R_{eq} = \frac{280}{11.4^2} = 2.15\ \Omega,\quad X_{eq} = \sqrt{6.58^2 - 2.15^2} = 6.22\ \Omega

Equivalent circuit (HV side): series Req=2.15ΩR_{eq}=2.15\,\Omega and Xeq=6.22ΩX_{eq}=6.22\,\Omega in the line; shunt magnetising branch (R0,X0R_0, X_0) across the input, with core loss Pi=90P_i = 90 W from the OC test.

Losses at full load:

  • Core (iron) loss Pi=90 WP_i = 90\ \text{W} (OC test).
  • Full-load copper loss Pcu=I22Req=11.362×2.15=277.5 WP_{cu} = I_2^2 R_{eq} = 11.36^2 \times 2.15 = 277.5\ \text{W}.

Efficiency at full load, 0.8 pf:

η=25000×0.825000×0.8+90+277.5=2000020367.5=98.2%\eta = \frac{25000 \times 0.8}{25000 \times 0.8 + 90 + 277.5} = \frac{20000}{20367.5} = 98.2\%

Voltage regulation (0.8 pf lagging, cosϕ=0.8, sinϕ=0.6\cos\phi=0.8,\ \sin\phi=0.6):

%Reg=I2(Reqcosϕ+Xeqsinϕ)V2×100=11.36(2.15×0.8+6.22×0.6)2200×100\%\text{Reg} = \frac{I_2(R_{eq}\cos\phi + X_{eq}\sin\phi)}{V_2}\times100 = \frac{11.36(2.15\times0.8 + 6.22\times0.6)}{2200}\times100 =11.36×5.452200×100=2.82%= \frac{11.36 \times 5.45}{2200}\times100 = 2.82\%
transformersequivalent-circuitefficiency
3long12 marks

(a) With a neat sketch, explain the working principle and construction of a DC shunt generator. Derive the expression for the generated EMF. [6]

(b) A 220 V DC shunt motor draws a line current of 40 A on full load. The armature resistance is 0.25 Ω and the field resistance is 110 Ω. If the rated speed is 1200 rpm, determine the back EMF on full load and the speed at which the motor will run when the load is reduced such that the armature current falls to 20 A (assume flux constant). [6]

(a) DC Shunt Generator

Construction: Stationary part (yoke, poles with field windings) and rotating armature carrying conductors in slots, with a commutator and brushes. In a shunt generator the field winding (many turns of fine wire) is connected in parallel with the armature.

Working principle: Based on Faraday's law of electromagnetic induction. When the armature rotates in the magnetic field, the conductors cut flux and an EMF is induced. The commutator and brushes convert the internally generated AC into DC at the terminals. (Sketch: poles N-S on the stator, armature conductors between them, commutator + brushes feeding the field and load.)

EMF equation: Let PP = poles, ZZ = total armature conductors, ϕ\phi = flux/pole, NN = speed (rpm), AA = parallel paths. Flux cut per conductor per revolution =Pϕ= P\phi; revolutions per second =N/60= N/60. EMF per conductor =PϕN/60= P\phi N/60. With Z/AZ/A conductors in series per path:

Eg=PϕZN60A voltsE_g = \frac{P\phi Z N}{60 A}\ \text{volts}

(A=PA = P for lap, A=2A = 2 for wave winding.)

(b) DC Shunt Motor Numerical

Field current Ish=220110=2 AI_{sh} = \dfrac{220}{110} = 2\ \text{A}. Armature current (full load) Ia=ILIsh=402=38 AI_a = I_L - I_{sh} = 40 - 2 = 38\ \text{A}.

Back EMF at full load:

Eb1=VIaRa=22038×0.25=2209.5=210.5 VE_{b1} = V - I_a R_a = 220 - 38 \times 0.25 = 220 - 9.5 = 210.5\ \text{V}

When IaI_a falls to 20 A:

Eb2=22020×0.25=215 VE_{b2} = 220 - 20 \times 0.25 = 215\ \text{V}

Since EbNϕE_b \propto N\phi and flux is constant, N2N1=Eb2Eb1\dfrac{N_2}{N_1} = \dfrac{E_{b2}}{E_{b1}}:

N2=1200×215210.5=1225.7 rpmN_2 = 1200 \times \frac{215}{210.5} = 1225.7\ \text{rpm}
dc-machinesdc-motorcharacteristics
4long12 marks

(a) Define resonance in a series RLC circuit. Derive expressions for the resonant frequency, quality factor (Q) and bandwidth, and sketch the variation of current with frequency. [6]

(b) A series RLC circuit has R = 10 Ω, L = 0.1 H and C = 100 μF, connected across a 230 V variable-frequency supply. Calculate (i) the resonant frequency, (ii) the impedance at resonance, (iii) the current at resonance, and (iv) the quality factor and bandwidth of the circuit. [6]

(a) Series RLC Resonance

Definition: A series RLC circuit is in resonance when the inductive reactance equals the capacitive reactance (XL=XCX_L = X_C); the net reactance is zero, the impedance is minimum (Z=RZ = R), the current is maximum, and the circuit behaves purely resistively (current in phase with voltage).

Resonant frequency: Setting ω0L=1/ω0C\omega_0 L = 1/\omega_0 C:

ω0=1LCf0=12πLC\omega_0 = \frac{1}{\sqrt{LC}}\quad\Rightarrow\quad f_0 = \frac{1}{2\pi\sqrt{LC}}

Quality factor: ratio of reactive to resistive voltage at resonance:

Q=ω0LR=1ω0CR=1RLCQ = \frac{\omega_0 L}{R} = \frac{1}{\omega_0 C R} = \frac{1}{R}\sqrt{\frac{L}{C}}

Bandwidth (between half-power frequencies f1,f2f_1, f_2):

BW=f2f1=R2πL=f0QBW = f_2 - f_1 = \frac{R}{2\pi L} = \frac{f_0}{Q}

Current vs frequency: the current I=V/ZI = V/Z is a bell-shaped curve, zero at very low and very high frequency, rising to a sharp peak Imax=V/RI_{max}=V/R at f0f_0; the sharper the peak, the higher the Q.

(b) Numerical (R=10Ω, L=0.1R=10\,\Omega,\ L=0.1\,H, C=100μC=100\,\muF, V=230V=230\,V)

(i) Resonant frequency:

f0=12π0.1×100×106=12π105=50.3 Hzf_0 = \frac{1}{2\pi\sqrt{0.1 \times 100\times10^{-6}}} = \frac{1}{2\pi\sqrt{10^{-5}}} = 50.3\ \text{Hz}

(ii) Impedance at resonance: Z=R=10 ΩZ = R = 10\ \Omega.

(iii) Current at resonance: I=V/R=230/10=23 AI = V/R = 230/10 = 23\ \text{A}.

(iv) Quality factor and bandwidth:

Q=1RLC=1100.1100×106=1101000=3.16Q = \frac{1}{R}\sqrt{\frac{L}{C}} = \frac{1}{10}\sqrt{\frac{0.1}{100\times10^{-6}}} = \frac{1}{10}\sqrt{1000} = 3.16 BW=f0Q=50.33.16=15.9 HzBW = \frac{f_0}{Q} = \frac{50.3}{3.16} = 15.9\ \text{Hz}
ac-fundamentalsrlc-circuitresonance
B

Section B: Short Answer Questions

Attempt all / any as specified.

7 questions
5short6 marks

A balanced three-phase star-connected load of impedance (8 + j6) Ω per phase is connected to a 400 V, 50 Hz, three-phase supply. Determine the phase current, line current, power factor, and the total active and reactive power drawn by the load.

Balanced Star-Connected Load

Per-phase impedance Z=8+j6 ΩZ = 8 + j6\ \Omega, so Z=82+62=10 Ω|Z| = \sqrt{8^2+6^2} = 10\ \Omega, angle ϕ=tan1(6/8)=36.87\phi = \tan^{-1}(6/8) = 36.87^\circ.

Phase voltage (star): Vph=VL3=4003=231 VV_{ph} = \dfrac{V_L}{\sqrt3} = \dfrac{400}{\sqrt3} = 231\ \text{V}.

Phase current =VphZ=23110=23.1 A= \dfrac{V_{ph}}{|Z|} = \dfrac{231}{10} = 23.1\ \text{A}.

Line current (star: IL=IphI_L = I_{ph}) =23.1 A= 23.1\ \text{A}.

Power factor =cos36.87=RZ=810=0.8= \cos 36.87^\circ = \dfrac{R}{|Z|} = \dfrac{8}{10} = 0.8 (lagging).

Total active power:

P=3VLILcosϕ=3×400×23.1×0.8=12.8 kWP = \sqrt3\,V_L I_L \cos\phi = \sqrt3 \times 400 \times 23.1 \times 0.8 = 12.8\ \text{kW}

Total reactive power:

Q=3VLILsinϕ=3×400×23.1×0.6=9.6 kVARQ = \sqrt3\,V_L I_L \sin\phi = \sqrt3 \times 400 \times 23.1 \times 0.6 = 9.6\ \text{kVAR}
three-phasestar-deltapower
6short6 marks

An iron ring of mean circumference 60 cm and cross-sectional area 5 cm² has an air gap of 2 mm cut in it. The ring is wound with 500 turns. Taking the relative permeability of iron as 800, calculate the current required to produce a flux of 0.5 mWb in the air gap. Neglect leakage and fringing.

Composite Magnetic Circuit (Iron + Air Gap)

Given: mean circumference =60= 60\,cm, A=5cm2=5×104m2A = 5\,\text{cm}^2 = 5\times10^{-4}\,\text{m}^2, air gap lg=2l_g = 2\,mm, N=500N=500, μr=800\mu_r = 800, ϕ=0.5\phi = 0.5\,mWb.

Flux density (same in iron and gap, neglecting fringing):

B=ϕA=0.5×1035×104=1.0 TB = \frac{\phi}{A} = \frac{0.5\times10^{-3}}{5\times10^{-4}} = 1.0\ \text{T}

MMF for iron path (li=0.600.002=0.598l_i = 0.60 - 0.002 = 0.598\,m):

Hi=Bμ0μr=1.04π×107×800=995 A/mH_i = \frac{B}{\mu_0\mu_r} = \frac{1.0}{4\pi\times10^{-7}\times800} = 995\ \text{A/m} MMFi=Hili=995×0.598=595 At\text{MMF}_i = H_i\,l_i = 995 \times 0.598 = 595\ \text{At}

MMF for air gap:

Hg=Bμ0=1.04π×107=7.96×105 A/mH_g = \frac{B}{\mu_0} = \frac{1.0}{4\pi\times10^{-7}} = 7.96\times10^{5}\ \text{A/m} MMFg=Hglg=7.96×105×0.002=1592 At\text{MMF}_g = H_g\,l_g = 7.96\times10^{5}\times0.002 = 1592\ \text{At}

Total MMF =595+1592=2187 At= 595 + 1592 = 2187\ \text{At}.

Required current:

I=Total MMFN=2187500=4.37 AI = \frac{\text{Total MMF}}{N} = \frac{2187}{500} = 4.37\ \text{A}
magnetic-circuitsmmfreluctance
7short5 marks

State the superposition theorem and explain its limitations. Discuss why it cannot be applied directly to calculate power dissipated in a resistor.

Superposition Theorem

Statement: In any linear bilateral network containing more than one independent source, the response (current or voltage) in any element equals the algebraic sum of the responses produced by each independent source acting alone, with all other independent sources deactivated (voltage sources short-circuited, current sources open-circuited; internal resistances retained).

Limitations:

  • Applies only to linear circuits; not valid for non-linear elements (diodes, etc.).
  • Applicable only to current and voltage (linear responses), not directly to power.
  • Dependent (controlled) sources are not deactivated — they remain active.

Why it cannot be applied directly to power: Power is a non-linear (quadratic) function of current/voltage, P=I2RP = I^2 R. If a resistor carries I1I_1 from source 1 and I2I_2 from source 2, the total current is I=I1+I2I = I_1 + I_2, but

P=(I1+I2)2R=I12R+I22R+2I1I2RI12R+I22R.P = (I_1 + I_2)^2 R = I_1^2 R + I_2^2 R + 2I_1 I_2 R \neq I_1^2 R + I_2^2 R.

The cross term 2I1I2R2I_1I_2R is lost if powers are simply added. Hence superposition is used to find the net current/voltage first, and power is then computed from that resultant.

network-theoremssuperposition
8short6 marks

Compare the construction and operating principle of a Permanent Magnet Moving Coil (PMMC) instrument with a Moving Iron (MI) instrument. State, with reasons, why a PMMC instrument cannot be used directly for AC measurement and how its range is extended for measuring large currents.

PMMC vs Moving-Iron (MI) Instruments

FeaturePMMCMoving Iron (MI)
Operating principleForce on current-carrying coil in a permanent-magnet field (motor action)Magnetic force on soft-iron piece in a field set up by the coil current
Moving elementCoil (carries current)Iron vane (attraction/repulsion type)
Field sourcePermanent magnetCurrent-carrying fixed coil
Deflecting torqueTdIT_d \propto ITdI2T_d \propto I^2
ScaleUniform (linear)Non-uniform (cramped at low end)
SupplyDC onlyAC and DC
Accuracy/power useHigh accuracy, low consumptionLower accuracy, higher consumption

Why PMMC cannot measure AC directly: Its deflecting torque is proportional to the instantaneous current and reverses direction with the current. On AC, the average torque over a cycle is zero, so the pointer merely vibrates around zero and reads nothing. (AC can be measured only with a rectifier or thermocouple ahead of the PMMC movement.)

Range extension for large currents: A low-value shunt resistance is connected in parallel with the meter coil so that most of the current bypasses the delicate coil, and only a fixed small fraction flows through it. For multiplier ratio m=I/Imm = I/I_m, the shunt is Rsh=Rmm1R_{sh} = \dfrac{R_m}{m - 1}, where RmR_m is the coil resistance.

measuring-instrumentspmmcmoving-iron
9short5 marks

A 3-phase, 4-pole, 50 Hz induction motor runs at 1440 rpm on full load. Calculate the synchronous speed, the slip, and the frequency of the rotor EMF. Briefly explain why an induction motor can never run at synchronous speed.

3-Phase Induction Motor

Given: P=4P = 4 poles, f=50f = 50\,Hz, N=1440N = 1440\,rpm.

Synchronous speed:

Ns=120fP=120×504=1500 rpmN_s = \frac{120 f}{P} = \frac{120 \times 50}{4} = 1500\ \text{rpm}

Slip:

s=NsNNs=150014401500=0.04=4%s = \frac{N_s - N}{N_s} = \frac{1500 - 1440}{1500} = 0.04 = 4\%

Rotor EMF frequency:

fr=sf=0.04×50=2 Hzf_r = s f = 0.04 \times 50 = 2\ \text{Hz}

Why it cannot run at synchronous speed: At synchronous speed the rotor would move exactly with the rotating stator field, so there would be no relative motion, no flux cutting, no rotor EMF, no rotor current and hence no torque. The motor would decelerate. A small slip is therefore always needed to maintain the rotor current and torque; for this reason the induction motor is also called an asynchronous motor.

ac-machinesinduction-motorslip
10short6 marks

(a) Define average value, RMS value and form factor of an alternating quantity, and derive the form factor of a sinusoidal voltage. [3]

(b) Explain the concept of power factor and discuss two practical methods used to improve the power factor of an industrial load. [3]

(a) Average, RMS and Form Factor

  • Average value: the mean of the instantaneous values over half a cycle (for a symmetrical wave); Vav=1T0TvdtV_{av} = \dfrac{1}{T}\int_0^T v\,dt over the relevant interval.
  • RMS value: the equivalent DC value that produces the same heating effect; Vrms=1T0Tv2dtV_{rms} = \sqrt{\dfrac{1}{T}\int_0^T v^2\,dt}.
  • Form factor: kf=VrmsVavk_f = \dfrac{V_{rms}}{V_{av}}.

Sinusoid v=Vmsinθv = V_m\sin\theta:

Vav=2Vmπ=0.637Vm,Vrms=Vm2=0.707VmV_{av} = \frac{2V_m}{\pi} = 0.637\,V_m,\qquad V_{rms} = \frac{V_m}{\sqrt2} = 0.707\,V_m kf=0.707Vm0.637Vm=1.11k_f = \frac{0.707\,V_m}{0.637\,V_m} = 1.11

(b) Power Factor and Its Improvement

Power factor is the cosine of the phase angle ϕ\phi between voltage and current, cosϕ=P/S\cos\phi = P/S (active power / apparent power). A low (lagging) pf means large reactive current, higher line losses, larger kVA demand and poor voltage regulation.

Two practical improvement methods:

  1. Static capacitor bank connected in parallel with the inductive load: the leading capacitive current cancels part of the lagging reactive current, raising the pf.
  2. Synchronous condenser (an over-excited synchronous motor running on no load): it draws leading reactive power and improves pf, useful for large bulk loads. (Phase-advancers on wound-rotor induction motors are another accepted method.)
ac-fundamentalspower-factorphasor
11short6 marks

(a) Explain the difference between a two-winding transformer and an auto-transformer, and state the principal advantages and one limitation of an auto-transformer. [3]

(b) Distinguish between hysteresis loss and eddy current loss in a transformer core, and state how each is minimized in practice. [3]

(a) Two-Winding Transformer vs Auto-Transformer

  • Two-winding transformer: primary and secondary are electrically isolated; energy is transferred entirely by magnetic (mutual) induction through separate windings.
  • Auto-transformer: has a single tapped winding common to both sides; part of the winding is shared, so energy is transferred by both magnetic induction and direct electrical (conductive) connection.

Advantages of auto-transformer: less copper and iron (cheaper, lighter, smaller); lower copper and iron losses, hence higher efficiency; better voltage regulation; useful for small voltage ratios (starters, voltage regulation).

Limitation: no electrical isolation between primary and secondary — a fault/break in the common winding can place full primary voltage on the secondary, which is unsafe for large ratios.

(b) Hysteresis Loss vs Eddy-Current Loss

Hysteresis lossEddy-current loss
CauseRepeated reversal of magnetisation of the core (molecular friction)Circulating currents induced in the core by the alternating flux
ExpressionPh=KhBm1.6fVP_h = K_h\,B_m^{1.6}\,f\,VPe=KeBm2f2t2VP_e = K_e\,B_m^{2}\,f^{2}\,t^{2}\,V
Minimised byUsing silicon steel / soft magnetic material with a narrow hysteresis loopLaminating the core (thin insulated sheets) to break up current paths and using high-resistivity steel

Both together constitute the core (iron) loss, which is essentially constant at constant voltage and frequency.

transformersauto-transformerlosses

Frequently asked questions

Where can I find the BE Computer Engineering (IOE, TU) Basic Electrical Engineering (IOE, EE 451) question paper 2079?
The full BE Computer Engineering (IOE, TU) Basic Electrical Engineering (IOE, EE 451) 2079 (regular) question paper is available free on Kekkei. You can read every question online and attempt the paper under timed exam conditions.
Does the Basic Electrical Engineering (IOE, EE 451) 2079 paper come with solutions?
Yes. Every question on this Basic Electrical Engineering (IOE, EE 451) past paper includes a step-by-step solution, plus instant AI feedback when you attempt it on Kekkei.
How many marks is the BE Computer Engineering (IOE, TU) Basic Electrical Engineering (IOE, EE 451) 2079 paper?
The BE Computer Engineering (IOE, TU) Basic Electrical Engineering (IOE, EE 451) 2079 paper carries 80 full marks and is meant to be completed in 180 minutes, across 11 questions.
Is practising this Basic Electrical Engineering (IOE, EE 451) past paper free?
Yes — reading and attempting this Basic Electrical Engineering (IOE, EE 451) past paper on Kekkei is completely free.